HK56-3PS-K Series 3 inch Air Actuated Ball Valve Tri-Clamp Connection
Spec.
- No MOQ required
- Size Range: 3/8″ to 4″
- Pressure Rating: 1000 WOG
- Body Material: 304 Stainless Steel
Air Actuated Ball Valve
2 way, 304 stainless steel ball valve (3 piece) with clamp connections and a double acting pneumatic actuator.
- Rack and pinion design pneumatic actuator
- Full port
- Investment casting body
- ISO 5211 direct mounting pad
- Blow-out proof stem
- Anti static device
Actuator Type | Single Acting (Spring Return), Double Acting |
---|---|
Size Range | 1/2″ to 4″ |
Body Material | Stainless Steel, WCB |
Ball Material | Stainless Steel |
Sealing Material | PTFE |
End Connection | Tri-Clamp |
The actuator on my automated valve operates, but the valve won’t turn. Why?
Most likely the valve stem or actuator coupling is broken.
Why doesn’t my valve open or close completely when the actuator operates it?
The electric actuator limit switches or the pneumatic actuator position stops are not correctly adjusted.
When I energize the solenoid on my pneumatic actuated valve, the valve won’t turn. How come?
Probably because there is no air pressure to the solenoid or dirt has jammed it. Also, debris might be trapped inside the valve. Or, the air pressure is not sufficient to operate the actuator. Remember: measure air pressure at the actuator, not at the compressor.
Can I buy an actuator from one manufacturer and mount it to a valve from another manufacturer?
Maybe. First, be sure that the actuator torque output is sufficient to turn the valve reliably. Second, you will have to fabricate a custom mounting bracket and coupling to connect the actuator to the valve.
What happens if I lose power to my electric actuator in the middle of an actuation cycle?
The valve will stop somewhere between full open and close. When power is reapplied to the original circuit, the actuator will complete the cycle.
I ordered a fail open pneumatic actuated valve by mistake. I needed a fail closed one. What can I do?
To make the change just remove the actuator from the valve and turn it, or the valve stem, 90 degrees and remount the actuator.
I’ve installed my automated valve in the line, but now I don’t know if the valve is in the open or closed position. How can I find out?
Remove the actuator from the valve and check the valve stem. Most ball valves have stem flats at right angles to the flow when the valve is in the off position. On butterfly valves check the stem flow arrow marking.
Do I have to have the solenoid valve that controls the air supply to my pneumatic actuator mounted right on the actuator?
Remove the actuator from the valve and check the valve stem. Most ball valves have stem flats at right angles to the flow when the valve is in the off position. On butterfly valves check the stem flow arrow marking.
How do I wire up my electric actuator?
Check the electric wiring schematic that came with the actuator for the correct hookup. Sometimes a copy is inside the actuator cover. If it is missing, don’t guess about the connections. Call the manufacturer for a schematic.
I’ve just installed an electric actuated valve and when I power it, it turns the valve 360 degrees and won’t shut off. What’s wrong?
The actuator is wired incorrectly (check the schematic accompanying the actuator), or the external control switch is not the correct type for the actuator.
My electric actuators cycle time is way too fast, can I slow it down?
Not unless you bought it with an optional speed control.
I just replaced a solenoid valve with an electric actuated valve and it won’t work. Why?
Actuators and solenoid valves require different types of electrical control switches. SPDT for actuators, SPST for solenoids. Check the actuator wiring schematic for the correct wiring and switch type.
Contact Us
About Us
Create since 2000, We first started as a solenoid valves manufacturer. Over decades of research and development,
COVNA has become the China market leader in quarter turn actuator and automatic control valve products.
Contact Info
info@covna-china.com
Telephone
+86-0769-22763199
Mobile
+86-1355-6646018
Address
Building C, Longchang Micro-Chuang Yuan, No.26 Hangtang Street, Dongguan, China
Products
Newsletter
Copyright © COVNA-VALVE-Privacy-Policy
This website uses cookies to improve your experience. We'll assume you're ok with this, but you can opt-out if you wish. Read More
- Always ActiveNecessary cookies help make a website usable by enabling basic functions like page navigation and access to secure areas of the website. The website cannot function properly without these cookies.
- Marketing cookies are used to track visitors across websites. The intention is to display ads that are relevant and engaging for the individual user and thereby more valuable for publishers and third party advertisers.
- Analytics cookies help website owners to understand how visitors interact with websites by collecting and reporting information anonymously.
- Preference cookies enable a website to remember information that changes the way the website behaves or looks, like your preferred language or the region that you are in.
- Unclassified cookies are cookies that we are in the process of classifying, together with the providers of individual cookies.